<p style="clear: both"><a class="image-link" href="http://dissolvedair.com/wp-content/uploads/2009/08/image1.jpg"><img class="linked-to-original" style=" display: inline; float: left; margin: 0 10px 10px 0;" src="http://dissolvedair.com/wp-content/uploads/2009/08/image1-thumb.jpg" alt="" width="120" height="119" align="left" /></a><a title="Dissolved Air Flotation" href="http://www.ptecserve.com">Dissolved Air Flotation</a> (DAF) has proven very effective for algae removal. These summaries are clear illustrations of actual DAF pilot studies that were done on lagoon systems. The analytical results are all from composite samples taken during the pilot test runs.</p>
<strong>Case Study # 1</strong>
Influent - 22 mg/l BOD; 79 mg/l TSS
DAF Effluent - 4 mg/l BOD; 4 mg/l TSS
Removal efficiencies - BOD 82%; TSS 95%
Sludge % moisture: 7 %
<strong>Chemicals used:</strong> 65 ppm aluminum chlorhydrate (ACH) and 4 ppm cationic polymer.
<strong>Notes:</strong> This customer was experiencing slow percolation rates caused by algae solids. In addition, they had a discharge limit of 60 mg/l TSS to their percolation ponds.
The ACH coagulant was chosen because of high alkalinity content of the water. The site is in an area of limestone. ACH works well in high alkaline conditions. However, the price is relatively expensive, ($0.25/lb) versus alum or ferric ($0.07/lb).
<strong>Percolation Test:</strong> Multiple clear PVC columns were set up vertically and filled with sand filter media. Thirty gallons of sample were poured into a separate column for each test, and then the column was again filled with the sample. The water level was then timed for the number of seconds the sample took to drop one foot in the column.
<p style="clear: both">DAF Effluent - 4 mg/l BOD; 4 mg/l TSS; 0.82 mg/l Phos; 1.91 mg/l TKN; 6 ntu Turbidity</p>
Removal efficiencies - BOD 82%; TSS 95%; 52% Phos; 79% TKN; 95% Turbidity
Sludge % moisture: 8.4%
<strong>Chemicals used:</strong> 4 ppm cationic polymer only
Notes: DAF evaluation was prompted by a state imposed limit of 45 mg/l TSS to discharge into a river. The bulk of the residual TSS in the effluent was daphnia "water fleas" that was visible to the eye.
<strong>Case Study # 3</strong>
Influent - 11 mg/l BOD; 30 mg/l TSS; 4.26 mg/l Phos; 24.9 ntu Turbidity
DAF Effluent - 0.25 mg/l BOD; 3 mg/l TSS; 0.71 mg/l Phos; 1.5 ntu Turbidity
Removal efficiencies - BOD 98%; TSS 90%; 83% Phos; 94% Turbidity
Sludge % moisture: 8.4%
<strong>Chemicals used: </strong>50 ppm aluminum sulfate and 2 ppm cationic polymer
Notes: <a title="DAV Design and Application" href="http://www.ptecserve.com">DAF evaluation</a> to solve problems with existing sand filters being plugged with algae floc.
<p style="clear: both">This article illustrates successful DAF application in algae removal.</p>
<br class="final-break" style="clear: both" />
<a title="Dissolved Air Flotation DAF" href="http://www.ptecserve.com">Dissolved Air Flotation</a>
<a title="Low Cost DAF Pumps Design for Economical Use" href="http://www.keystec.com">DAF Pumps</a>
Is expensive frequent pump replacement a given for DAF applications? No!
Not with the KeysTec AirWhip brand Aeration Pump.
<div><span class="ws12">The </span><span class="ws12" ><strong><em>KT - M Series Air-Whip Pump</em></strong></span></div>
<div><span class="ws12">is the industry's solution for all these typical DAF implementations:</span></div>
<ul>
<li><span class="ws12">Short pump life</span></li>
<li><span class="ws12">High Cost</span></li>
<li><span class="ws12">Complexity</span></li>
<li><span class="ws12">Intolerance of Entrained Solids</span></li>
<li><span class="ws12">Difficult or Impossible Maintenance</span></li>
</ul>
<div><span class="ws12">The </span><span class="ws12" ><strong><em>KT - M Series Air-Whip Pump</em></strong></span></div>
<div><span class="ws12" ><strong><em></em></strong></span><span class="ws12">provides the following:</span></div>
<ul>
<li><span class="ws12">Lower Initial Cost</span></li>
<li><span class="ws12">Lower Maintenance Cost</span></li>
<li><span class="ws12">Simplicity</span></li>
<li><span class="ws12">Easily Passes Entrained Solids</span></li>
<li><span class="ws12">Flexibility in Operation Modes</span></li>
<li><span class="ws12">Very Long Life Expectancy</span></li>
</ul>
Most of our pumps are still in operation 2 years plus from day one of installation and <strong>they cost a fraction of their standard counterparts!</strong>
<strong><span style="font-weight: normal;">More about <a title="Low Cost DAF Pump Dissolved Air Flotation" href="http://www.keystec.com/Air_Whip.html">Low Cost DAF Pump</a> AirWhip by KeysTec.</span></strong>
dwk0619a
<h1><span><img src="http://www.keystec.com/images/impeller%20reduced%20LQ.jpg" border="0" alt="" width="220" height="214" /></span></h1>
All DAF (<em>Dissolved </em>Air Flotation) installations have basic requirements. In order to achieve maximum dissolved air in the water, the following must be available:
<span>• </span>Significant air to water surface area interface (achieved within the pump)
<span>• </span>Pressure, provided by the pump (preferably 75 to 115 psi., depending on installation and design)
<span>• </span>Time. Dissolving air is not instantaneous. It requires time under pressure and interface. This is the purpose of the saturation tank/pressure header.
For very large DAF installations having very high flows, the Air-Whip pump is capable of delivering flows to match the “white water” requirement up to about 400 GPM. It must be understood that as the flow increases, the residence time in the pump decreases, placing more dependence on the saturation vessel part of the system. In some cases, the client has simply injected directly into the influent line of the DAF with no problem generating “white water”. This can work if the flow through the Air-Whip pump is relatively low. For higher flows, a tank or larger diameter section of pipe of sufficient length must be provided to introduce sufficient residence time under pressure for the sheared air to be dissolved into the water. In many of the modern DAFs, this saturation tank is the pressure header from which “white water” is delivered to multiple points. All properly designed DAFs have some type of saturation vessel for this purpose. Some are capped large diameter pipe sections and some are tanks, but they serve the same specific purpose. An installation without this device can never perform to full capability.
Contact KeysTec, LLC to review the details of your installation to determine suitability for conversion to the Air-Whip. In many cases, the “Full Flow” or “Split Flow” configuration can give you a significant increase in the capacity of your DAF.
<a title="dissolved air flotation" href="http://dissolvedair.com">Dissolved Air Flotation</a>
Note: DAFs are sometimes used in conjunction with sand filters. This is yet an emerging concept that has known issues. Typically, sand filters are used for certain metallic compounds:
Vietnam and Bangladesh are both confronted with high arsenic concentrations, but distinct water compositions require different solutions. Arsenic mitigation depends for the most part on natural factors, such as the availability of alternative water sources and the feasibility of water treatment.  If several options are available, socioeconomic factors determine which mitigation option is implemented most successfully.
The socially accepted and already widespread sand filters in the Red River delta have advantages for their simplicity and low cost of operation. The removal of iron from the pumped water is immediately apparent even to people who are not aware of the arsenic problem. Thus, sand filters are a good option in Vietnam and in other affected regions with high concentrations of dissolved iron.
source: <a title="sand filters" href="http://washtech.wordpress.com/2008/09/29/arsenic-mitigation-bangladesh-and-vietnam-different-groundwater-compositions-require-different-approaches/">washtec.wordpress.com</a>
Use of sand filters must be carefully evaluated and specifications must be strictly followed.
KT-M-2-1/2 X2 Replacement of OEM Grudfos Pumps - Four precision environmental DAFs. 75-200 GPM in recycle mode.
Indiana based Co. application in cooked bacon. Air-Whip pumps in service 2 years.
5 pumps installed on 4 DAFs. Completely.
Wastewater is <span><strong>not <span style="font-weight: normal;"><span><strong>screened</strong></span>. </span></strong></span>
<span><strong><span style="font-weight: normal;">Significant process solids (cracked pepper, meat scraps, trash) are entrained in the water, but passes through the pump without harm.</span></strong></span>
All AirWhip pumps are still in operation.
<ul>
<li>Focus on problem areas where solutions are too costly or perform poorly.</li>
<li>Keep the designed solutions as simple as possible increasing product reliability</li>
<li>Provide solutions that use readily available, low cost components wherever possible for ease of maintenance and low initial cost.</li>
</ul>
Our products bear the stamp of this philosophy - the KeysTec Air-Ship pump has demonstrated this philosophy with in service times <a href="http://www.keystec.com/files/Installations%20Report.pdf">measured in years</a> instead of months.
<a title="dissolved air flotation" href="http://www.keystec.com">Dissolved Air Flotation</a>
The synthesis of KeysTec principles was formed through decades of experience in Industrial Waste Water Treatment systems, analysis and innovation in equipment and system design. Our background in Dissolved Air Flotation application and design was partnered with expertise in information technology, Industrial Control and Process Engineering & Control has  allowed us to bring dynamic innovative and practical solutions to the industry, taking advantage of the latest technology and producing cost saving solutions of exponential scale.
<h3>Our Philosophy Is Dynamic</h3>
We adapt to demands and change in the industry with innovative technological approaches.
<address><a style="color:#acf;" title="dissolved air flotation" href="http://www.keystec.com"><span style="font-family: mceinline;">dissolved air flotation</span></a></address>
<a style="color:#acf;font:italic .7em verdana;" title="Orange County Web Design" href="http://davekeys.com">Orange County Web Design</a>
KeysTec, LLC was formed by Daniel (Dan) Keys in 2004> Dan envisioned a purpose of developing and marketing innovative solutions to the Industrial Waste Water Treatment Industry's most difficult and elusive problems.
Dan served the Industrial Waste Water Treatment industry in a variety of capacities for over 20 years. Then KeysTec, LLC became the quantum leap to the application of sensible engineering principles to the many problems continuing to plague the industry.
<img src="http://www.keystec.com/images/impeller%20reduced%20LQ.jpg" border="0" alt="" width="220" height="214" />
<span >kt0608</span>
No comments:
Post a Comment